Industrial Power
Click the link below to download the file.
Get your files as below link
Dowload link
24V
240W
10A
3 x 320-575 Vac (3-Phase) or 2 x 340-575 Vac (2-Phase)
124 x 50 x 125.3 mm
4.88” x 1.97” x 4.93”
0.84 kg (1.85 lb)
Model | Description |
---|---|
DRF-24V240W3GTA | Spring Clamp Terminal |
24V
240W
10A
3 x 320-575 Vac (3-Phase) or 2 x 340-575 Vac (2-Phase)
124 x 50 x 125.3 mm
4.88” x 1.97” x 4.93”
0.84 kg (1.85 lb)
Model | Description |
---|---|
DRF-24V240W3GTA | Spring Clamp Terminal |
Output Current
10A
|
Output Voltage
24V
|
Output Voltage Range
|
Output Voltage Adjustment Range
24-28 Vdc
|
Output Power
240W
|
Output Current Adjustment Range
|
Max Output Voltage
|
Buffering Time
-
|
Line Regulation
< 40 mV (@ 3 x 320-575 Vac input, 100% load)
|
Load Regulation
< 150 mV (@ 3 x 320-575 Vac input, 0-100% load)
|
PARD
< 100 mVpp
|
Start-up Time
1,000 ms typ. @ nominal input (100% load)
|
Hold-up Time
20 ms typ. @ 3 x 400 Vac (100% load)
40 ms typ. @ 3 x 500 Vac (100% load) |
Dynamic Response (Overshoot & Undershoot O/P Voltage)
± 5% @ 3 x 320-575 Vac input, 0-100% load (Slew Rate: 0.1 A/μs, 50% duty cycle @ 5 Hz to 1 kHz)
|
Start-up with Capacitive Loads
10,000 µF Max
|
Remote ON/OFF
-
|
Protective Device
-
|
Voltage Drop Between Input and Output
-
|
Residual Ripple/PARD (20MHz)
-
|
Residual Ripple
-
|
Max. Power
-
|
Ripple & Noise
-
|
LED System Voltage Range in CC Mode
-
|
Rise Time
50 ms typ. @ nominal input (100% load)
|
Power Boost Duration
-
|
Power Boost Recovery Time
-
|
Nominal Input Voltage
3 x 380-500 Vac
|
Input Voltage Range
3 x 320-575 Vac (3-Phase) or 2 x 340-575 Vac (2-Phase)
|
Max Input Voltage
-
|
Nominal Input Frequency
50-60 Hz
|
Input Frequency Range
47-63Hz
|
Nominal DC Input Voltage
|
DC Input Voltage Range
450-800 Vdc
|
Input Current
< 0.75 A @ 3 x 400 Vac,
< 0.65 A @ 3 x 500 Vac |
Input Power (Standby Mode)
-
|
Efficiency at 100% load
89.5% typ. @ 3 x 400 Vac & 3 x 500 Vac
|
Inrush Current
20 A typ. @ 3 x 400 Vac, 25 A typ, @ 3 x 500 Vac
|
Charging Time
-
|
Power Factor at 100% load
> 0.50 @ 3 x 400 Vac & 3 x 500 Vac
|
Leakage Current
< 3.5 mA @ 3 x 500 Vac
|
Nominal Current
-
|
Total Harmonic Distortion
-
|
Power Dissipation
0% load: < 2.7 W @ 3 x 400 Vac & 3 x 500 Vac
100% load: < 26.5 W @ 3 x 400 Vac & 3 x 500 Vac |
Efficiency @ 10% load
-
|
Case Chassis / Cover
Aluminum
|
|
Indicator
Green LED DC OK
|
|
Cooling System
Convection
|
|
Input Terminal
4 Pins (Rated 600 V / 30 A)
|
|
Output Terminal
4 Pins (Rated 600 V / 30 A)
|
|
Signal Terminal
2 Pins (Rated 300 V / 12 A)
|
|
Noise Sound Pressure Level (SPL)
< 25 dBA
|
|
Input/Output Terminal
-
|
|
Signal
-
|
|
Mounting Rail
Standard TS35 DIN Rail in accordance with EN 60715
|
|
Wire
Input: AWG 18-10
Output: AWG 16-10 Signal: AWG 20-16 |
|
Protection Structure
-
|
|
Terminal
-
|
|
Unit Weight
0.84 kg (1.85 lb)
|
Dimensions
124 x 50 x
125.3 mm
4.88” x 1.97” x 4.93” |
Vibration (Operating)
IEC 60068-2-6, Sine Wave: 10-500 Hz; 3G peak; 60 min per axis for all X, Y, Z directions
|
Shock Test (Operating)
-
|
Operating Temperature
3-Phase
-40°C to +70°C 2-Phase -40°C to +60°C |
Storage Temperature
-40°C to +85°C
|
Power De-rating
Vertical Mounting: > 55°C de-rate power by 3.33% / °C
Horizontal Mounting: > 40°C de-rate power by 2.5% / °C Input Voltage: 2-Phase < 2 x 380 Vac de-rate power by 0.5% / V |
Operating Humidity
5 to 95% RH (Non-Condensing)
|
Shock Test (Non-Operating)
IEC 60068-2-27, Half Sine Wave: 50 G for duration of 11 ms; 3 times per direction
|
Vibration (Non-Operating)
-
|
Storage Humidity
-
|
Operating Altitude
OVC III
0 to 2,500 Meters (8,200 ft.) OVC II 2,500 to 6,000 Meters (19,680 ft.) 0 to 5,000 Meters (16,400 ft.) |
Pollution Degree
2
|
Bump Test (Operating)
-
|
Over Voltage Category
IEC/EN 62477-1, EN 60204-1, IEC 62103
OVC III: 0 to 2,500 Meters (8,200 ft.) OVC II: 2,500 to 6,000 Meters (19,680 ft.) IEC/EN 62368-1, IEC/EN 61010 OVC II: 0 to 5,000 Meters (16,400 ft.) |
Corrosion
-
|
Overvoltage
< 35 V, Hiccup Mode, Non-Latching (Auto-Recovery)
|
Overload / Overcurrent
105 - 150% of rated load current, Auto-recovery
Continuous current limit Mode (Vo > 80%) |
Over Temperature
60°C-80°C Surrounding Air Temperature @ 100% load, Non-Latching (Auto-Recovery)
|
Short Circuit
Hiccup Mode, Non-Latching (Auto-Recovery when the fault is removed)
|
Reverse Polarity Protection
-
|
Degree of Protection
IP20
|
Protection Against Shock
Class I with Primary Earth connection
|
Input Polarity Protection
-
|
Battery Polarity Protection
-
|
Wrong Battery Voltage Protection
-
|
Deep Discharge Protection
-
|
Overload
-
|
Overcurrent
-
|
Internal Fuse
-
|
Insufficient Input Voltage Protection
-
|
MTBF
Telcordia SR-332: > 700,000 hrs.
I/P: 3 x 400 Vac & 3 x 500 Vac, O/P: 100% load, Ta: 25°C |
Expected Cap Life Time
10 Years
I/P: 3 x 400 Vac & 3 x 500 Vac, O/P: 24 V, 5 A, Ta: 40°C |
Safety Certificate
-
|
Electrical Safety
SIQ Bauart: EN 62368-1, EN 61010-1, EN 61010-2-201, EN 62477-1
UL/cUL recognized: UL 62368-1 and CSA C22.2 No. 62368-1 (File No. E191395) CB scheme: IEC 60950-1, IEC 62368-1, IEC 61010-1, IEC 61010-2-201 UKCA: BS EN 62368-1, BS EN 61010-1, BS EN 61010-2-201 EAC: TP TC 004/2011 BIS: IS 13252 (Part 1) |
CE
In conformance with EMC Directive 2014/30/EU and Low Voltage Directive 2014/35/EU
|
Medical Safety
-
|
Galvanic Isolation
Input to Output: 4.0 kVac
Input to Ground: 2.0 kVac Output to Ground: 1.5 kVac DC OK relay contact to Output: 0.5 kVac DC OK relay contact to Ground: 1.5 kVac |
Industrial Control Equipment
-
|
Hazardous Location / ATEX
-
|
II 3 G ATEX 2014/34/EU
-
|
Electrical Equipments of Machines
EN/BS EN 60204-1 (over voltage category III)
|
Electrical Equipment for Use in Electrical Power Installations
IEC/EN/BS EN 62477-1 / IEC 62103
|
Safety Entry Low Voltage
SELV (IEC 60950-1)
|
Maritime
-
|
Material and Parts
-
|
Isolation Resistance
-
|
PE Resistance
-
|
UKCA
In conformance with Electrical Equipment (Safety) Regulations 2016 No. 1011 and The Electromagnetic Compatibility Regulations 2016 No. 1091
|
Certificates for Other Countries
-
|
BIS
-
|
KC
-
|
Electrical Equipment for Measurement, Control, and Laboratory Use
UL 61010-1, UL 61010-2-201 (File No. E315355)
|
ITE Safety
-
|
SIL3
-
|
Emission
CE & RE)
Generic Standards: EN/BS EN 61000-6-3, CISPR 32, EN/BS EN 55032, KS C 9832, FCC Title 47: Class B |
Immunity
Generic Standards: EN/BS EN 55024, EN/BS EN 55035, KS C 9835, EN/BS EN 61000-6-1
|
Harmonic Current Emissions
IEC/EN/BS EN 61000-3-2, Class A
|
Voltage Fluctuation and Flicker
IEC/EN/BS EN 61000-3-3
|
ESD Immunity
-
|
Radiated Immunity
-
|
EFT
-
|
Surge
-
|
Conducted Immunity
-
|
Magnetic Field
-
|
Voltage Dips
-
|
Component Power Supply for General Use
EN/BS EN 61204-3
|
12V
24W
2A
85-264 Vac
12V
15W
1.25A
85-264 Vac
12V
54W
4.5A
85-264 Vac
24V
60W
2.5A
85-264 Vac