Industrial Power
Click the link below to download the file.
Get your files as below link
Dowload link
24V
960W
40A
85-264Vac
124 x 125 x 133.6 mm
4.88” x 4.92” x 5.26”
2.87 kg (6.33 lb)
24V
960W
40A
85-264Vac
124 x 125 x 133.6 mm
4.88” x 4.92” x 5.26”
2.87 kg (6.33 lb)
Output Current
40A
|
Output Voltage
24V
|
Output Voltage Range
|
Output Voltage Adjustment Range
24-28Vdc
|
Output Power
960W
|
Output Current Adjustment Range
|
Max Output Voltage
|
Buffering Time
-
|
Line Regulation
10mV Max. (@ 85-264Vac input, 100% load)
|
Load Regulation
50mV Max. (@ single mode, 0-100% load)
1000mV Typ. (@ parallel mode, 0-100% load) |
PARD
100mVpp Max.
|
Start-up Time
800ms Max. @ 100Vac & 120Vac & 230Vac
|
Hold-up Time
24ms Typ. @ 100Vac & 120Vac & 230Vac (100% load)
|
Dynamic Response (Overshoot & Undershoot O/P Voltage)
± 5% @ 0.7-40A load
Slew rate 0.1A/µs (@ 5Hz, 50Hz & 1kHz, 50% Duty Cycle) |
Start-up with Capacitive Loads
40,000µF Max.
|
Remote ON/OFF
-
|
Protective Device
-
|
Voltage Drop Between Input and Output
-
|
Residual Ripple/PARD (20MHz)
-
|
Residual Ripple
-
|
Max. Power
-
|
Ripple & Noise
-
|
LED System Voltage Range in CC Mode
-
|
Rise Time
75ms Max. @ 100Vac & 120Vac & 230Vac (0µF, 24V, 40A)
75ms Max. @ 100Vac & 120Vac & 230Vac (40,000µF, 24V, 40A) |
Power Boost Duration
5 seconds Typ.
7 seconds Max. |
Power Boost Recovery Time
17 seconds Typ.
|
Nominal Input Voltage
100-240Vac
|
Input Voltage Range
85-264Vac
|
Max Input Voltage
-
|
Nominal Input Frequency
50-60Hz
|
Input Frequency Range
47-63Hz
|
Nominal DC Input Voltage
|
DC Input Voltage Range
-
|
Input Current
10.50A Typ. @ 100Vac, 8.60A Typ. @ 120Vac, 4.50A Typ. @ 230Vac
|
Input Power (Standby Mode)
-
|
Efficiency at 100% load
94.10% Typ. @ 100Vac, 94.71% Typ. @ 120Vac, 95.98% Typ. @ 230Vac
|
Inrush Current
11A Max. @ 100Vac, 13A Max. @ 120Vac, 20A Max. @ 230Vac
|
Charging Time
-
|
Power Factor at 100% load
0.99 Typ. @ 100Vac, 0.99 Typ. @ 120Vac, 0.96 Typ. @ 230Vac
|
Leakage Current
(Enclosure to Neutral)
0.50mA / 1.21mA @ 110Vac, 50Hz, TN/TT system / IT system 0.71mA / 1.73mA @ 132Vac, 50Hz, TN/TT system / IT system 1.18mA / 2.82mA @ 264Vac, 50Hz, TN/TT system / IT system |
Nominal Current
-
|
Total Harmonic Distortion
-
|
Power Dissipation
0% load:
5.58W Typ. @ 100Vac, 4.61W Typ. @ 120Vac, 3.70W Typ. @ 230Vac 13.9W Max. @ 100Vac, 13.1W Max. @ 120Vac, 13.2W Max. @ 230Vac 100% load: 60.32W Typ. @ 100Vac, 53.71W Typ. @ 120Vac, 40.21W Typ. @ 230Vac 70.00W Max. @ 100Vac, 65.60W Max. @ 120Vac, 54.80W Max. @ 230Vac |
Efficiency @ 10% load
-
|
Case Chassis / Cover
Aluminium
|
|
Indicator
Green LED (DC OK) and Red LED (Overload)
|
|
Cooling System
Convection
|
|
Input Terminal
3 Pins (Rated 600V/35A)
|
|
Output Terminal
4 Pins (Rated 300V/65A)
|
|
Signal Terminal
5 Pins (Rated 300V/10A)
|
|
Noise Sound Pressure Level (SPL)
< 25dBA
|
|
Input/Output Terminal
-
|
|
Signal
-
|
|
Mounting Rail
Standard TS35 DIN Rail in accordance with EN 60715
|
|
Wire
Input: AWG 14-8
Output: AWG: 10-6 Signal: AWG 20-16 |
|
Protection Structure
-
|
|
Terminal
-
|
|
Unit Weight
2.87 kg (6.33 lb)
|
Dimensions
124 x 125 x
133.6 mm
4.88” x 4.92” x 5.26” |
Vibration (Operating)
-
|
Shock Test (Operating)
-
|
Operating Temperature
-25°C to +70°C (Cold start -40°C)
|
Storage Temperature
-40°C to +85°C
|
Power De-rating
Vertical Mounting:
Temperature: > 60°C de-rate power by 2.5% / °C Input Voltage: If < 90Vac, > 55°C de-rate power by 1.67% / °C Horizontal Mounting: Temperature: > 40°C de-rate power by 1.67% / °C Input Voltage: If < 90Vac, > 35°C de-rate power by 1.43% / °C |
Operating Humidity
5 to 95% RH (Non-Condensing)
|
Shock Test (Non-Operating)
IEC 60068-2-27, Half Sine Wave: 30G for a duration of 18ms; 3 times per direction, 6 times in total
|
Vibration (Non-Operating)
IEC 60068-2-6, Sine Wave: 10-500Hz; 3G peak; displacement of 0.35mm; 60 min per axis for all X, Y, Z directions
|
Storage Humidity
-
|
Operating Altitude
0 to 5,000 Meters (16,400 ft.)
0 to 2,500 Meters (8,200 ft.) for IEC/EN 61558 |
Pollution Degree
2
|
Bump Test (Operating)
IEC 60068-2-29, Half Sine Wave: 10G for a duration of 11ms, 1,000 times per direction, 6,000 times in total
|
Over Voltage Category
III
According to IEC/EN 62477-1 / EN 60204-1 (clearance and creepage distances) and IEC 62103 (safety part) |
Corrosion
-
|
Overvoltage
< 32V, SELV Output, Hiccup Mode, Non-Latching (Auto- Recovery)
|
Overload / Overcurrent
> 150% of rated load current, Constant current, Hiccup Mode (Auto-Recovery)
|
Over Temperature
< 80°C Surrounding Air Temperature @ 100% load, Non-Latching (Auto-Recovery)
|
Short Circuit
Hiccup Mode, Non-Latching (Auto-Recovery when the fault is removed)
|
Reverse Polarity Protection
-
|
Degree of Protection
IP20
|
Protection Against Shock
Class I with Primary Earth connection
|
Input Polarity Protection
-
|
Battery Polarity Protection
-
|
Wrong Battery Voltage Protection
-
|
Deep Discharge Protection
-
|
Overload
-
|
Overcurrent
-
|
Internal Fuse
-
|
Insufficient Input Voltage Protection
-
|
MTBF
513,800 hrs. (I/P: 100Vac, O/P: 24V, 40A, Ta: 25°C)
312,900 hrs. (I/P: 100Vac, O/P: 24V, 40A, Ta: 40°C) |
Expected Cap Life Time
131,400 hrs. @ 100Vac & 230Vac (O/P: 24V, 40A, Ta: 25°C)
131,400 hrs. @ 100Vac & 230Vac (O/P: 24V, 20A, Ta: 25°C) 60,000 hrs. @ 100Vac (O/P: 24V, 40A, Ta: 40°C) 92,000 hrs. @ 230Vac (O/P: 24V, 40A, Ta: 40°C) 131,400 hrs. @ 100Vac (O/P: 24V, 20A, Ta: 40°C) 115,400 hrs. @ 230Vac (O/P: 24V, 20A, Ta: 40°C) |
Safety Certificate
-
|
Electrical Safety
SIQ Bauart: EN 62368-1, EN 61558-1, EN 61558-2-16, EN 61010-1, EN 61010-2-201
UL/cUL recognized: UL 60950-1 and CSA C22.2 No. 60950-1 (File No. E191395), UL 62368-1 and CSA C22.2 No. 62368-1 (File No. E191395) CB scheme: IEC 60950-1, IEC 62368-1, IEC 61558-1, IEC 61558-2-16, IEC 61010-1, IEC 61010-2-201 UKCA: BS EN 62368-1, BS EN 61558-1, BS EN 61558-2-16, BS EN 61010-1, BS EN 61010-2-201 |
CE
In conformance with EMC Directive 2014/30/EU and Low Voltage Directive 2014/35/EU
|
Medical Safety
-
|
Galvanic Isolation
Input / Output: 4.54KVac
Input / PE: 2.5KVac Input / DC OK relay contact: 4.54KVac (Recommend to connect DC OK pins together with output pins) Output / PE: 1.5KVac Output / DC OK relay contact: 0.5KVac DC OK relay contact / PE: 1.5KVac |
Industrial Control Equipment
UL/cUL listed: UL 508 and CSA C22.2 No. 107.1-01 (File No. E315355)
CSA: CSA C22.2 No. 107.1-01 (File No. 181564) |
Hazardous Location / ATEX
-
|
II 3 G ATEX 2014/34/EU
-
|
Electrical Equipments of Machines
EN/BS EN 60204-1 (over voltage category III)
|
Electrical Equipment for Use in Electrical Power Installations
IEC/EN/BS EN 62477-1 / IEC 62103
|
Safety Entry Low Voltage
SELV (IEC 60950-1)
|
Maritime
DNV GL: Germanischer Lloyd classified
ABS: American Bureau for Shipping) PDA Environmental category: C, EMC2 |
Material and Parts
-
|
Isolation Resistance
> 5MOhm (Input to Output, 500Vdc)
|
PE Resistance
< 0.1Ohm
|
UKCA
In conformance with Electrical Equipment (Safety) Regulations 2016 No. 1011 and The Electromagnetic Compatibility Regulations 2016 No. 1091
|
Certificates for Other Countries
-
|
BIS
-
|
KC
-
|
Electrical Equipment for Measurement, Control, and Laboratory Use
-
|
ITE Safety
-
|
SIL3
-
|
Emission
(CE & RE)
Generic Standards: EN/BS EN 61000-6-3 CISPR 32, EN/BS EN 55032, KN 32, CISPR 11, EN/BS EN 55011, FCC Title 47: Class B |
Immunity
Generic Standards: EN/BS EN 55024, KN 35, EN/BS EN 61000-6-2
|
Harmonic Current Emissions
IEC/EN/BS EN 61000-3-2, Class A
|
Voltage Fluctuation and Flicker
IEC/EN/BS EN 61000-3-3
|
ESD Immunity
-
|
Radiated Immunity
-
|
EFT
-
|
Surge
-
|
Conducted Immunity
-
|
Magnetic Field
-
|
Voltage Dips
-
|
Component Power Supply for General Use
EN/BS EN 61204-3
|
5V
12W
2.4A
85-264 Vac
48V
480W
10A
3 x 320-575 Vac
24V
15W
0.63A
85-264 Vac
48V
960W
20A
3 x 320-575 Vac