Industrial Power
Click the link below to download the file.
Get your files as below link
Dowload link
24V
240W
10A
2 x 180-550Vac (2-Phase)
180-305Vac (Single Phase)
124 x 60 x 117 mm
4.88” x 2.36” x 4.61”
0.81 kg (1.79 lb)
24V
240W
10A
2 x 180-550Vac (2-Phase)
180-305Vac (Single Phase)
124 x 60 x 117 mm
4.88” x 2.36” x 4.61”
0.81 kg (1.79 lb)
Output Current
10A
|
Output Voltage
24V
|
Output Voltage Range
|
Output Voltage Adjustment Range
24-28Vdc
|
Output Power
240W
|
Output Current Adjustment Range
|
Max Output Voltage
|
Buffering Time
-
|
Line Regulation
< 0.5% (@ 200-550Vac input, 100% load)
|
Load Regulation
< 1.0% (@ 200-550Vac input, 0-100% load)
|
PARD
< 150mVpp @ -10°C and above
< 200mVpp @ below -10°C |
Start-up Time
< 1,000ms @ nominal input (100% load)
|
Hold-up Time
> 18ms @ 2 x 230Vac,
> 30ms @ 2 x 400Vac (100% load) |
Dynamic Response (Overshoot & Undershoot O/P Voltage)
± 5% @ 180-550Vac input, 0-100% load
(Slew Rate: 0.1A/μs, 50% duty cycle @ 5Hz) |
Start-up with Capacitive Loads
10,000µF Max
|
Remote ON/OFF
-
|
Protective Device
-
|
Voltage Drop Between Input and Output
-
|
Residual Ripple/PARD (20MHz)
-
|
Residual Ripple
-
|
Max. Power
-
|
Ripple & Noise
-
|
LED System Voltage Range in CC Mode
-
|
Rise Time
-
|
Power Boost Duration
-
|
Power Boost Recovery Time
-
|
Nominal Input Voltage
2 x 200-500Vac (2-Phase)
200-277Vac (Single Phase) |
Input Voltage Range
2 x 180-550Vac (2-Phase)
180-305Vac (Single Phase) |
Max Input Voltage
-
|
Nominal Input Frequency
50-60Hz
|
Input Frequency Range
47-63Hz
|
Nominal DC Input Voltage
|
DC Input Voltage Range
254-780Vdc
|
Input Current
< 2.00A @ 2 x 230Vac,
< 1.00A @ 2 x 400Vac |
Input Power (Standby Mode)
-
|
Efficiency at 100% load
> 90.0% @ 2 x 400Vac
|
Inrush Current
< 50A @ 2 x 200Vac & 2 x 500Vac
|
Charging Time
-
|
Power Factor at 100% load
-
|
Leakage Current
< 3.5mA @ 500Vac
|
Nominal Current
-
|
Total Harmonic Distortion
-
|
Power Dissipation
0% load: < 8.5W @ 2 x 200Vac, < 9.5W @ 2 x 500Vac
100% load: < 26.5W @ 2 x 200Vac, < 21.5W @ 2 x 500Vac |
Efficiency @ 10% load
-
|
Case Chassis / Cover
Aluminium
|
|
Indicator
Green LED (DC OK)
|
|
Cooling System
Convection
|
|
Input Terminal
3 Pins (Rated 600V/35A)
|
|
Output Terminal
4 Pins (Rated 300V/28A)
|
|
Signal Terminal
-
|
|
Noise Sound Pressure Level (SPL)
< 40dBA
|
|
Input/Output Terminal
-
|
|
Signal
-
|
|
Mounting Rail
Standard TS35 DIN Rail in accordance with EN 60715
|
|
Wire
Input: AWG 18-8
Output: AWG 16-12 (ensure that all output terminals are connected) |
|
Protection Structure
-
|
|
Terminal
-
|
|
Unit Weight
0.81 kg (1.79 lb)
|
Dimensions
124 x 60 x
117 mm
4.88” x 2.36” x 4.61” |
Vibration (Operating)
-
|
Shock Test (Operating)
-
|
Operating Temperature
-30°C to +70°C
|
Storage Temperature
-40°C to +85°C
|
Power De-rating
Vertical: > 50°C de-rate power by 2.25% / °C
Horizontal: > 30°C de-rate power by 2% / °C Input Voltage: < 200Vac de-rate power by 0.5% / Vac |
Operating Humidity
5 to 95% RH (Non-Condensing)
|
Shock Test (Non-Operating)
IEC 60068-2-27, 30G (300m/S²) for a duration of 18ms,
1 times per direction, 2 times in total |
Vibration (Non-Operating)
IEC 60068-2-6, 10Hz to 500Hz @ 30m/S² (3G peak);
60 min per axis for all X, Y, Z direction |
Storage Humidity
-
|
Operating Altitude
0 to 2,500 Meters (8,200 ft.) for ITE application (@ 50°C)
0 to 2,000 Meters (6,560 ft.) for Industrial application (@ 50°C) |
Pollution Degree
2
|
Bump Test (Operating)
IEC 60068-2-29, Half Sine Wave: 10G for a duration of 11ms, 1,000 times per direction, 6,000 times in total
|
Over Voltage Category
III
According to IEC/EN 62477-1 / EN 60204-1 (clearance and creepage distances) and IEC 62103 (safety part) |
Corrosion
-
|
Overvoltage
32V ±10%, SELV Output, Hiccup Mode, Non-Latching (Auto-Recovery)
|
Overload / Overcurrent
> 120-180% of rated load current, Constant current, Hiccup Mode (Auto-Recovery)
|
Over Temperature
< 80°C Surrounding Air Temperature @ 100% load, Non-Latching (Auto-Recovery)
|
Short Circuit
Hiccup Mode, Non-Latching (Auto-Recovery when the fault is removed)
|
Reverse Polarity Protection
-
|
Degree of Protection
IP20
|
Protection Against Shock
Class I with Primary Earth connection
|
Input Polarity Protection
-
|
Battery Polarity Protection
-
|
Wrong Battery Voltage Protection
-
|
Deep Discharge Protection
-
|
Overload
-
|
Overcurrent
-
|
Internal Fuse
-
|
Insufficient Input Voltage Protection
-
|
MTBF
> 500,000 hrs. as per Telcordia SR-332 (I/P: 2 x 200Vac & 500Vac, O/P: 100% load, Ta: 25°C)
|
Expected Cap Life Time
10 years (2 x 200Vac & 500Vac, 50% load @ 40°C)
|
Safety Certificate
-
|
Electrical Safety
SIQ Bauart: EN 62368-1
UL/cUL recognized: UL 60950-1 and CSA C22.2 No. 60950-1 (File No. E191395), UL 62368-1 and CSA C22.2 No. 62368-1 (File No. E191395) CB scheme: IEC 60950-1, IEC 62368-1 UKCA: BS EN 62368-1 |
CE
In conformance with EMC Directive 2014/30/EU (only AC input) and Low Voltage Directive 2014/35/EU
|
Medical Safety
-
|
Galvanic Isolation
Input to Output: 4.0 KVac
Input to Ground: 2.0 KVac Output to Ground: 1.5 KVac |
Industrial Control Equipment
UL/cUL listed: UL 508 and CSA C22.2 No. 107.1-01 (File No. E315355)
CSA: CSA C22.2 No. 107.1-01 (File No. 181564) |
Hazardous Location / ATEX
-
|
II 3 G ATEX 2014/34/EU
-
|
Electrical Equipments of Machines
EN/BS EN 60204-1 (over voltage category III)
|
Electrical Equipment for Use in Electrical Power Installations
IEC/EN/BS EN 62477-1 / IEC 62103
|
Safety Entry Low Voltage
SELV (IEC 60950-1)
|
Maritime
-
|
Material and Parts
-
|
Isolation Resistance
-
|
PE Resistance
-
|
UKCA
In conformance with Electrical Equipment (Safety) Regulations 2016 No. 1011 and The Electromagnetic Compatibility Regulations 2016 No. 1091
|
Certificates for Other Countries
-
|
BIS
-
|
KC
-
|
Electrical Equipment for Measurement, Control, and Laboratory Use
-
|
ITE Safety
-
|
SIL3
-
|
Emission
(CE & RE)
Generic Standards: CISPR 32, EN/BS EN 55032, CISPR 11, EN/BS EN 55011, FCC Title 47: Class B |
Immunity
Generic Standards: EN/BS EN 55024, EN/BS EN 61000-6-2
|
Harmonic Current Emissions
IEC/EN/BS EN 61000-3-2, Class A
|
Voltage Fluctuation and Flicker
IEC/EN/BS EN 61000-3-3
|
ESD Immunity
-
|
Radiated Immunity
-
|
EFT
-
|
Surge
-
|
Conducted Immunity
-
|
Magnetic Field
-
|
Voltage Dips
-
|
Component Power Supply for General Use
EN/BS EN 61204-3
|
200-550V
600W
2A
198-440Vac
12V
24W
2A
85-264 Vac
12V
85.2W
7.1A
85-264 Vac
24V
36W
1.5A
85-264 Vac