Industrial Power
Click the link below to download the file.
Get your files as below link
Dowload link
24V
60W
2.5A
3 x 320-600Vac
121 x 50 x 117.3 mm
4.76” x 1.97” x 4.62”
0.66 kg (1.46 lb)
Model | Description |
---|---|
DRP024V060W3BN | Without Class I, Div 2 and ATEX |
24V
60W
2.5A
3 x 320-600Vac
121 x 50 x 117.3 mm
4.76” x 1.97” x 4.62”
0.66 kg (1.46 lb)
Model | Description |
---|---|
DRP024V060W3BN | Without Class I, Div 2 and ATEX |
Output Current
2.5A
|
Output Voltage
24V
|
Output Voltage Range
|
Output Voltage Adjustment Range
24-28Vdc
|
Output Power
60W
|
Output Current Adjustment Range
|
Max Output Voltage
|
Buffering Time
-
|
Line Regulation
< 0.5% (@ 3 x 320-600Vac input, 100% load)
|
Load Regulation
< 1.0% (@ 3 x 320-600Vac input, 0-100% load)
|
PARD
< 150mVpp
|
Start-up Time
< 1,000ms @ nominal input (100% load)
|
Hold-up Time
> 20ms @ 3 x 400Vac,
> 40ms @ 3 x 500Vac (100% load) |
Dynamic Response (Overshoot & Undershoot O/P Voltage)
± 5% @ 3 x 320-600Vac input, 0-100% load
(Slew Rate: 0.1A/μs, 50% duty cycle @ 5Hz to 1KHz) |
Start-up with Capacitive Loads
10,000µF Max
|
Remote ON/OFF
-
|
Protective Device
-
|
Voltage Drop Between Input and Output
-
|
Residual Ripple/PARD (20MHz)
-
|
Residual Ripple
-
|
Max. Power
-
|
Ripple & Noise
-
|
LED System Voltage Range in CC Mode
-
|
Rise Time
< 100ms @ nominal input (100% load)
|
Power Boost Duration
-
|
Power Boost Recovery Time
-
|
Nominal Input Voltage
3 x 400-500Vac
|
Input Voltage Range
3 x 320-600Vac
|
Max Input Voltage
-
|
Nominal Input Frequency
50-60Hz
|
Input Frequency Range
47-63Hz
|
Nominal DC Input Voltage
|
DC Input Voltage Range
450-800Vdc
|
Input Current
< 0.30A @ 3 x 400Vac,
< 0.25A @ 3 x 500Vac |
Input Power (Standby Mode)
-
|
Efficiency at 100% load
> 86.0% @ 3 x 400Vac & 3 x 500Vac
|
Max Inrush Current
< 30A @ 3 x 400Vac & 3 x 500Vac
|
Charging Time
-
|
Power Factor at 100% load
-
|
Leakage Current
< 3.5mA @ 500Vac
|
Nominal Current
-
|
Total Harmonic Distortion
-
|
Max Power Dissipation
0% load: < 3.0W @ 3 x 400Vac, < 4.0W @ 3 x 500Vac
100% load: < 8.7W @ 3 x 400Vac & 3 x 500Vac |
Efficiency @ 10% load
-
|
Case Chassis / Cover
Aluminium
|
|
Indicator
Green LED (DC OK)
|
|
Cooling System
Convection
|
|
Input Terminal
4 Pins (Rated 600V/35A)
|
|
Output Terminal
4 Pins (Rated 300V/28A)
|
|
Signal Terminal
-
|
|
Noise Sound Pressure Level (SPL)
< 40dBA
|
|
Input/Output Terminal
-
|
|
Signal
-
|
|
Mounting Rail
Standard TS35 DIN Rail in accordance with EN 60715
|
|
Wire
Input / Output: AWG 18-12
|
|
Protection Structure
-
|
|
Terminal
-
|
|
Unit Weight
0.66 kg (1.46 lb)
|
Dimensions
121 x 50 x
117.3 mm
4.76” x 1.97” x 4.62” |
Vibration (Operating)
-
|
Shock Test (Operating)
-
|
Operating Temperature
-25°C to +80°C (Cold Start at -40°C)
|
Storage Temperature
-40°C to +85°C
|
Power De-rating
Vertical: > 50°C de-rate power by 2.5% / °C, > 70°C de-rate power by 5%/ °C
Horizontal: > 45°C de-rate power by 2.5% / °C, > 55°C de-rate power by 1.66% / °C, > 70°C de-rate power by 5% / °C |
Operating Humidity
5 to 95% RH (Non-Condensing)
|
Shock Test (Non-Operating)
IEC 60068-2-27, 30G (300m/S²) for a duration of 18ms, 1 times per direction, 2 times in total
|
Vibration (Non-Operating)
IEC 60068-2-6, 10Hz to 500Hz @ 30m/S² (3G peak); 60 min per axis for all X, Y, Z direction
|
Storage Humidity
-
|
Operating Altitude
0 to 2,500 Meters (8,200 ft.) for ITE application
0 to 2,000 Meters (6,560 ft.) for Industrial application |
Pollution Degree
2
|
Bump Test (Operating)
IEC 60068-2-29, Half Sine Wave: 10G for a duration of 11ms, 1,000 times per direction, 6,000 times in total
|
Over Voltage Category
III
According to IEC/EN 62477-1 / EN 60204-1 (clearance and creepage distances) and IEC 62103 (safety part) |
Corrosion
-
|
Overvoltage
32V ±10%, SELV Output, Hiccup Mode, Non-Latching (Auto-Recovery)
|
Overload / Overcurrent
> 150% of rated load current, Hiccup Mode, Non-Latching (Auto-Recovery)
|
Over Temperature
< 80°C Surrounding Air Temperature @ 100% load, Non-Latching (Auto-Recovery)
|
Short Circuit
Hiccup Mode, Non-Latching (Auto-Recovery when the fault is removed)
|
Reverse Polarity Protection
-
|
Degree of Protection
IP20
|
Protection Against Shock
Class I with Primary Earth connection
|
Input Polarity Protection
-
|
Battery Polarity Protection
-
|
Wrong Battery Voltage Protection
-
|
Deep Discharge Protection
-
|
Overload
-
|
Overcurrent
-
|
Internal Fuse
-
|
Insufficient Input Voltage Protection
-
|
MTBF
> 800,000 hrs. as per Telcordia SR-332 (I/P: 3 x 400Vac, O/P: 100% load, Ta: 25°C)
|
Expected Cap Life Time
10 years (3 x 400Vac & 3 x 500Vac, 50% load @ 40°C)
|
Safety Certificate
-
|
Electrical Safety
SIQ Bauart: EN 62368-1
UL/cUL recognized: UL 60950-1 and CSA C22.2 No. 60950-1 (File No. E191395), UL 62368-1 and CSA C22.2 No. 62368-1 (File No. E191395) CB scheme: IEC 60950-1, IEC 62368-1 UKCA: BS EN 62368-1 |
CE
In conformance with EMC Directive 2014/30/EU and Low Voltage Directive 2014/35/EU
For DRP024V060W3BA: In conformance with Equipment for explosive atmospheres (ATEX) directive 2014/34/EU |
Medical Safety
-
|
Galvanic Isolation
Input to Output 4.0KVac
Input to Ground 2.0KVac Output to Ground 1.5KVac |
Industrial Control Equipment
UL/cUL listed: UL 508 and CSA C22.2 No. 107.1-01 (File No. E315355)
CSA: CSA C22.2 No. 107.1-01 (File No. 181564) |
Hazardous Location / ATEX
(For DRP024V060W3BA)
cCSAus: CSA C22.2 No. 213-M1987 and ANSI / ISA 12.12.01:2007 [Class I, Division 2, Group A, B, C, D T4, Ta = -25°C to +80°C (Vertical: > +50°C derating, Horizontal: > +45°C derating)] ATEX: EN 60079-0:2012, EN 60079-15:2010 [II 3G Ex nA IIC T4 Gc, Ta= -25°C to +80°C (Vertical: > +50°C derating, Horizontal: > +45°C derating)] Certificate No. EPS 13 ATEX 1 575 X |
II 3 G ATEX 2014/34/EU
-
|
Electrical Equipments of Machines
EN/BS EN 60204-1 (over voltage category III)
|
Electrical Equipment for Use in Electrical Power Installations
IEC/EN/BS 62477-1 / IEC 62103
|
Safety Entry Low Voltage
SELV (IEC 60950-1)
|
Maritime
-
|
Material and Parts
-
|
Isolation Resistance
-
|
PE Resistance
-
|
UKCA
In conformance with Electrical Equipment (Safety) Regulations 2016 No. 1011 and The Electromagnetic Compatibility Regulations 2016 No. 1091
|
Certificates for Other Countries
-
|
BIS
-
|
KC
-
|
Electrical Equipment for Measurement, Control, and Laboratory Use
-
|
ITE Safety
-
|
SIL3
-
|
Emission
(CE & RE)
Generic Standards: CISPR 32, EN/BS EN 55032, CISPR 11, EN/BS EN 55011, FCC Title 47: Class B |
Immunity
Generic Standards: EN/BS EN 55024, EN/BS EN 61000-6-2
|
Harmonic Current Emissions
IEC/EN/BS EN 61000-3-2, Class A
|
Voltage Fluctuation and Flicker
IEC/EN/BS EN 61000-3-3
|
ESD Immunity
-
|
Radiated Immunity
-
|
EFT
-
|
Surge
-
|
Conducted Immunity
-
|
Magnetic Field
-
|
Voltage Dips
-
|
Component Power Supply for General Use
EN 61204-3
|
24V
91.92W
3.83A
85-264 Vac
48V
480W
10A
3 x 320-575 Vac
24V
480W
20A
85-276 Vac
48V
92.16W
1.92A
85-264 Vac