Industrial Power
Click the link below to download the file.
Get your files as below link
Dowload link
24V
1500W
62.5A
90-264 Vac
204 x 127 x 40.5 mm
8.03” x 5.00” x 1.59”
1.5 kg (3.31 lb)
24V
1500W
62.5A
90-264 Vac
204 x 127 x 40.5 mm
8.03” x 5.00” x 1.59”
1.5 kg (3.31 lb)
Output Current
62.5A
|
Output Voltage
24V
|
Output Voltage Range
|
Output Voltage Adjustment Range
24-28 Vdc
|
Output Power
1500W
|
Output Current Adjustment Range
|
Max Output Voltage
|
Buffering Time
-
|
Line Regulation
± 0.5%
|
Load Regulation
± 1%
|
PARD
<1% Vrated pk-pk @ rated load
|
Start-up Time
1000 ms @ 115 Vac, 500 ms @ 230 Vac
|
Hold-up Time
16 ms @ 1200 W load, 115 Vac
12 ms @ 1500 W load, 230 Vac |
Dynamic Response (Overshoot & Undershoot O/P Voltage)
± 10% @ with 5-100% load change
|
Start-up with Capacitive Loads
6,000 µF
|
Remote ON/OFF
-
|
Protective Device
-
|
Voltage Drop Between Input and Output
-
|
Residual Ripple/PARD (20MHz)
-
|
Residual Ripple
-
|
Max. Power
-
|
Ripple & Noise
-
|
LED System Voltage Range in CC Mode
-
|
Rise Time
<50 ms
|
Power Boost Duration
-
|
Power Boost Recovery Time
-
|
Peak Power
2,200 W peak for 3 sec, @ 180~264 Vac
|
Nominal Input Voltage
100-240 Vac
|
Input Voltage Range
90-264 Vac
|
Max Input Voltage
-
|
Nominal Input Frequency
50-60 Hz
|
Input Frequency Range
47-63Hz
|
Nominal DC Input Voltage
|
DC Input Voltage Range
-
|
Input Current
15 A max.
|
Input Power (Standby Mode)
1.5 W typ. @ 230 Vac
|
Efficiency at 100% load
91.0% typ. @ 230 Vac
|
Inrush Current
40 A @ 264 Vac, cold/hot start
|
Charging Time
-
|
Power Factor at 100% load
0.99 @ 115 V/50 Hz, 0.98 @ 230 V/50 Hz
|
Leakage Current
< 0.5 mA @ 240Vac
|
Nominal Current
-
|
Total Harmonic Distortion
-
|
Power Dissipation
-
|
Efficiency @ 10% load
-
|
Case Chassis / Cover
SGCC / SGCC
|
|
Indicator
Green LED (DC OK)
|
|
Cooling System
Force Cooling
|
|
Input Terminal
M 4.0 x 3 Pins, CN1 / AC Input
|
|
Output Terminal
M 3.5 x 4 Pins, CN101 / DC Output
|
|
Signal Terminal
-
|
|
Noise Sound Pressure Level (SPL)
-
|
|
Input/Output Terminal
-
|
|
Signal
-
|
|
Mounting Rail
-
|
|
Wire
8 AWG*5 (2X)
|
|
Protection Structure
-
|
|
Terminal
-
|
|
Unit Weight
1.5 kg (3.31 lb)
|
Dimensions
204 x 127 x
40.5 mm
8.03” x 5.00” x 1.59” |
Vibration (Operating)
IEC 60068-2-6, Sine Wave: 5 Hz to 500 Hz @ 2G; 15 min for X, Y, Z direction
|
Shock Test (Operating)
-
|
Operating Temperature
-20°C to +70°C
|
Storage Temperature
-40°C to +85°C
|
Power De-rating
Temperature: > 50°C de-rate power by 2% / °C
Input: 1,500W @ 180-264Vac; 1,200W @ 180-100Vac; 1,200W de-rate power by 1.33%/Vac @ 90-100Vac; 1,000W @ 90Vac |
Operating Humidity
20 to 90% (Non-Condensing)
|
Shock Test (Non-Operating)
IEC 60068-2-27, Half Sine Wave: 50 G for duration of 11 ms; 3 times per direction
|
Vibration (Non-Operating)
-
|
Storage Humidity
-
|
Operating Altitude
0 to 5,000 Meters (0 to 16,400 ft)
|
Pollution Degree
2
|
Bump Test (Operating)
-
|
Over Voltage Category
-
|
Corrosion
-
|
Acoustic Noise
< 45dB @ 80% load @ 25°C (Tolerance: ±2dB)
|
Overvoltage
Main output 145% of rated normal voltage, Latch Mode
|
Overload / Overcurrent
Main output 130% of rated load current, Hiccup Mode, Non-Latching (Auto-Recovery) Standby 3.2A max with Hiccup Mode (Auto-Recovery)
|
Over Temperature
Latch Mode for Main output
|
Short Circuit
Hiccup Mode to Main output / Standby
(Auto-Recovery when the fault is removed) |
Reverse Polarity Protection
-
|
Degree of Protection
-
|
Protection Against Shock
Class I with Protection Earth connection
|
Input Polarity Protection
-
|
Battery Polarity Protection
-
|
Wrong Battery Voltage Protection
-
|
Deep Discharge Protection
-
|
Overload
-
|
Overcurrent
-
|
Internal Fuse
T10 A / 250 V
|
Insufficient Input Voltage Protection
-
|
MTBF
500K hrs based on Telcordia SR-332 (@ 115 Vac, 1200W, 35°C)
|
Expected Cap Life Time
26,280 hrs, (@115 Vac, 1000W @ 25°C)
|
Safety Certificate
-
|
Electrical Safety
TUV Bauart: EN 62368-1, EN 60335-1 & IEC 61558-1/ -2-16
UL/cUL: UL 62368-1 and CAN/CSA C22.2 No. 62368-1 CB scheme: IEC 62368-1, IEC 60335-1 & IEC 61558-1/ -2-16 CCC: GB 17625.1 BIS: IS 13252 (Part 1) |
CE
In conformance with EMC Directive 2014/30/EU and Low Voltage Directive 2014/35/EU
|
Medical Safety
-
|
Galvanic Isolation
Input to Output: 4.0 KVac
Input to Ground: 1.5 KVac Output to Ground: 1.5 KVac |
Industrial Control Equipment
-
|
Hazardous Location / ATEX
-
|
II 3 G ATEX 2014/34/EU
-
|
Electrical Equipments of Machines
-
|
Electrical Equipment for Use in Electrical Power Installations
-
|
Safety Entry Low Voltage
SELV
|
Maritime
-
|
Material and Parts
-
|
Isolation Resistance
-
|
PE Resistance
-
|
UKCA
In conformance with Electromagnetic Compatibility Regulations 2016 and Electrical Equipment (Safety) Regulations 2016
|
Certificates for Other Countries
-
|
BIS
-
|
KC
-
|
Electrical Equipment for Measurement, Control, and Laboratory Use
-
|
ITE Safety
-
|
SIL3
-
|
Emission
EN 55035, KS C 9835
|
Immunity
EN/BS EN 55035, KS C 9835, & Compliance to EN/ BS EN 55014-2 , EN/BS EN 61000-6- 1 , EN/BS EN 61000-6-2
|
Harmonic Current Emissions
IEC/EN 61000-3-2, Meet Class A limit
|
Voltage Fluctuation and Flicker
EN 61000-3-3
|
ESD Immunity
-
|
Radiated Immunity
-
|
EFT
-
|
Surge
-
|
Conducted Immunity
-
|
Magnetic Field
-
|
Voltage Dips
-
|
Component Power Supply for General Use
-
|
24V
320W
13.4A
90-264 Vac
24V
240W
10A
90-264 Vac
24V
150W
6.5A
90-264 Vac
24V
600W
25A
90-264 Vac