Industrial Power
Click the link below to download the file.
Get your files as below link
Dowload link
4.2V
252W
60A
90-132Vac, 180-264Vac (Selectable by switch)
215 x 115 x 50 mm
8.46” x 4.53” x 1.97”
0.81 kg (1.79 lb)
** NRND **
PMT-4V350W1AM, PMT-4V350W1AMA, PMT-4V350W1AMB, PMT-4V350W1AMC, PMT-4V350W1AN
Model | Description |
---|---|
PMT-4V350W1AN | Front face connector |
PMT-4V350W1AMA | Terminal block with connector cover |
PMT-4V350W1AMB | Terminal block, conformal coating |
PMT-4V350W1AMC | Terminal block with connector cover, conformal coating |
** NRND **
PMT-4V350W1AM, PMT-4V350W1AMA, PMT-4V350W1AMB, PMT-4V350W1AMC, PMT-4V350W1AN
4.2V
252W
60A
90-132Vac, 180-264Vac (Selectable by switch)
215 x 115 x 50 mm
8.46” x 4.53” x 1.97”
0.81 kg (1.79 lb)
Model | Description |
---|---|
PMT-4V350W1AN | Front face connector |
PMT-4V350W1AMA | Terminal block with connector cover |
PMT-4V350W1AMB | Terminal block, conformal coating |
PMT-4V350W1AMC | Terminal block with connector cover, conformal coating |
Output Current
60A
|
Output Voltage
4.2V
|
Output Voltage Range
|
Output Voltage Adjustment Range
3.78-4.70Vdc
|
Output Power
252W
|
Output Current Adjustment Range
|
Max Output Voltage
|
Buffering Time
-
|
Line Regulation
± 0.5% typ.
|
Load Regulation
± 2.5% typ.
|
PARD
< 150mVpp
|
Start-up Time
< 1000ms @ nominal input (100% load)
|
Hold-up Time
> 16ms @ 115Vac,
> 20ms @ 230Vac |
Dynamic Response (Overshoot & Undershoot O/P Voltage)
± 1000mVpp @ 10-50% load and 50-100% load
|
Start-up with Capacitive Loads
8,000µF Max
|
Remote ON/OFF
-
|
Protective Device
-
|
Voltage Drop Between Input and Output
-
|
Residual Ripple/PARD (20MHz)
-
|
Residual Ripple
-
|
Max. Power
-
|
Ripple & Noise
-
|
LED System Voltage Range in CC Mode
-
|
Rise Time
-
|
Power Boost Duration
-
|
Power Boost Recovery Time
-
|
Peak Power
-
|
Nominal Input Voltage
100-120Vac, 200-240Vac (Selectable by Switch)
|
Input Voltage Range
90-132Vac, 180-264Vac (Selectable by switch)
|
Max Input Voltage
-
|
Nominal Input Frequency
50-60Hz
|
Input Frequency Range
47-63Hz
|
Nominal DC Input Voltage
|
DC Input Voltage Range
-
|
Input Current
< 7.00A @ 115Vac,
< 4.00A @ 230Vac |
Input Power (Standby Mode)
-
|
Efficiency at 100% load
> 75.0% @ 230Vac
|
Inrush Current
< 40A @ 115Vac,
< 60A @ 230Vac |
Charging Time
-
|
Power Factor at 100% load
-
|
Leakage Current
< 3.5mA @ 240Vac
|
Nominal Current
-
|
Total Harmonic Distortion
-
|
Power Dissipation
-
|
Efficiency @ 10% load
-
|
Case Chassis / Cover
Aluminium
|
|
Indicator
-
|
|
Cooling System
Forced Cooling
|
|
Input Terminal
-
|
|
Output Terminal
-
|
|
Signal Terminal
-
|
|
Noise Sound Pressure Level (SPL)
-
|
|
Input/Output Terminal
-
|
|
Signal
-
|
|
Mounting Rail
-
|
|
Wire
-
|
|
Protection Structure
-
|
|
Terminal
-
|
|
Unit Weight
0.81 kg (1.79 lb)
|
Dimensions
215 x 115 x
50 mm
8.46” x 4.53” x 1.97” |
Vibration (Operating)
IEC 60068-2-6, Sine Wave: 10Hz to 150Hz @ 25m/S² (2.5G peak); 90 min per axis for all X, Y, Z direction
|
Shock Test (Operating)
-
|
Operating Temperature
-20°C to +70°C
|
Storage Temperature
-40°C to +85°C
|
Power De-rating
> 50°C de-rate power by 4% / °C
> 60°C de-rate power by 1% / °C < 100Vac de-rate power by 3% / V, < 200Vac de-rate power by 1.5% / V |
Operating Humidity
< 95% RH (Non-Condensing)
|
Shock Test (Non-Operating)
IEC60068-2-27, Half Sine: 50G for a duration of 11ms, 3 times per direction,18 times in total
|
Vibration (Non-Operating)
IEC60068-2-6, Random: 5Hz to 500Hz @ 2.09Grms peak; 20 min per axis for all X, Y, Z direction
|
Storage Humidity
-
|
Operating Altitude
0 to 5,000 Meters (0 to 16,400 ft)
|
Pollution Degree
2
|
Bump Test (Operating)
-
|
Over Voltage Category
-
|
Corrosion
-
|
Acoustic Noise
-
|
Overvoltage
< 4.83~7.00V, SELV Output, Latch Mode
|
Overload / Overcurrent
105~175% of rated load current, Hiccup Mode, Non-Latching (Auto-Recovery)
|
Over Temperature
Hiccup Mode, Non-Latching (Auto-Recovery when the fault is removed)
|
Short Circuit
Hiccup Mode, Non-Latching (Auto-Recovery when the fault is removed)
|
Reverse Polarity Protection
-
|
Degree of Protection
-
|
Protection Against Shock
Class I with PE* connection
|
Input Polarity Protection
-
|
Battery Polarity Protection
-
|
Wrong Battery Voltage Protection
-
|
Deep Discharge Protection
-
|
Overload
-
|
Overcurrent
-
|
Internal Fuse
-
|
Insufficient Input Voltage Protection
-
|
MTBF
> 700,000 hrs. as per Telcordia SR-332
I/P: 100Vac, O/P: 100% load, Ta: 35°C |
Expected Cap Life Time
10 years (115Vac & 230Vac, 50% load @ 40°C)
|
Safety Certificate
-
|
Electrical Safety
UL/cUL recognized to UL60950-1 and CSA C22.2 No. 60950-1 (File no. E131881),
CB scheme to IEC60950-1 |
CE
-
|
Medical Safety
-
|
Galvanic Isolation
Input to Output: 3.0 KVac
Input to Ground: 1.5 KVac Output to Ground: 500 Vac |
Industrial Control Equipment
-
|
Hazardous Location / ATEX
-
|
II 3 G ATEX 2014/34/EU
-
|
Electrical Equipments of Machines
-
|
Electrical Equipment for Use in Electrical Power Installations
-
|
Safety Entry Low Voltage
-
|
Maritime
-
|
Material and Parts
RoHS Directive 2011/65/EU Compliant
|
Isolation Resistance
-
|
PE Resistance
-
|
UKCA
-
|
Certificates for Other Countries
-
|
BIS
-
|
KC
-
|
Electrical Equipment for Measurement, Control, and Laboratory Use
-
|
ITE Safety
-
|
SIL3
-
|
Emission
CISPR22, EN55022, FCC Title 47: Class A (Test with Delta EMI filter P/N: 10DKAW5)
|
Immunity
EN 55024
|
Harmonic Current Emissions
-
|
Voltage Fluctuation and Flicker
IEC/EN 61000-3-3
|
ESD Immunity
-
|
Radiated Immunity
-
|
EFT
-
|
Surge
-
|
Conducted Immunity
-
|
Magnetic Field
-
|
Voltage Dips
-
|
Component Power Supply for General Use
-
|
24V
1200W
-
85-264 Vac
24V
108W
4.5A
180-264 Vac
24V
52.8W
2.2A
180-264 Vac
48V
158.4W
3.3A
180-264 Vac